Wire Size Calculator

Enter the load, the volts and the one-way distance. You get the size the amps need, the size the distance needs, and the wire to use.

Your run

Smallest wire for your run and load

The larger of the two sizes is the one to use. Nothing you type leaves your browser.

System
Wire
V

Common: 120, 208, 240, 277, 480.

A

What the load draws, from its nameplate.

Load

Continuous means 3 hours or more, like an EV charger, a water heater or a heat strip. The wire is sized for 125% of its amps (NEC 210.19(A)(1)); enter the load's own amps, and the drop is worked at those.

ft

Panel to the load. The formula counts the return trip for you.

Terminal rating

Up to 100 A, use 60 °C unless the breaker, the device and the wire are all rated 75 °C. Over 100 A, the code uses 75 °C, and the calculator switches to it until you pick. NM cable (Romex) is held to 60 °C.

%

3% is the usual target for a branch circuit, 5% for feeder and branch together.

Result

-

Fill in the run above.

Size for the amps (60 °C)-
Size for drop within 3%-
Drop at the size to use-
Volts at the load-
Wire to use-

Sized from NEC Table 310.16 and voltage drop only. It does not cover conduit fill, more than three wires together, hot attics or roofs, or motor and equipment nameplate rules. Check your local code and the terminal ratings before you pull wire.

AWG sizes from 14 to 4/0

AWG numbers run backwards: the smaller the number, the thicker the wire. 14 AWG is the thinnest size this calculator uses and 4/0 (said "four aught") is the thickest. Each size has an area in circular mils, which sets its resistance, and an allowable current from the code tables, which sets how much it can carry without overheating.

Allowable amps by wire size (NEC Table 310.16)
Wire (AWG)Area (cmil)Copper 60 °C ampsCopper 75 °C ampsAlum. 60 °C ampsAlum. 75 °C amps
144,1101515--
126,53020201515
1010,38030302525
816,51040503540
626,24055654050
441,74070855565
352,620851006575
266,360951157590
183,69011013085100
1/0105,600125150100120
2/0133,100145175115135
3/0167,800165200130155
4/0211,600195230150180

The amps assume no more than three current-carrying wires together and 86 °F (30 °C) around them, with the breaker limits of NEC 240.4(D) on 14 to 10 AWG. Area is from NEC Chapter 9, Table 8. A dash means the size is not listed (14 AWG aluminum). The 60 °C columns apply to circuits of 100 A and under and to NM cable, unless every terminal on the circuit is rated 75 °C. Circuits over 100 A use the 75 °C columns (NEC 110.14(C)), and the calculator switches to them above 100 A. Example: 200 A on 240 V, 100 feet, copper, needs 3/0 (200 A at 75 °C), which drops 3.08 V (1.28%).

Copper vs aluminum

Aluminum carries less current than copper of the same size and has more resistance (a K of 21.2 against 12.9), so an aluminum run is usually one size larger in the common sizes. Example: 60 A on 240 V, 100 feet, with 75 °C terminals. Copper needs 6 AWG, which drops 5.90 V (2.46%). Aluminum needs 4 AWG, which drops 6.09 V (2.54%).

Aluminum is common for feeders and service wire because it costs less per foot at those sizes. It needs lugs and connectors rated for aluminum (marked AL or AL/CU) and the torque the maker lists. Switch the wire above to compare the two on your own run.

Check the voltage drop

The amps set the smallest size that is safe. The distance can push it bigger, because a thin wire on a long run loses too much voltage. This calculator checks both and gives you the larger:

  • 20 A on 120 V, 100 feet, copper. 12 AWG carries 20 A, but over 100 feet it drops 6.58%. 8 AWG keeps it to 2.6%, so 8 AWG is the wire to use.
  • 30 A on 240 V, 150 feet, copper. 10 AWG carries 30 A but drops 4.66%. 8 AWG drops 2.93%.
  • 50 A on 240 V, 150 feet, copper, 60 °C. 6 AWG carries 50 A but drops 3.07%, just over. 4 AWG drops 1.93%.

For a chart of every size on your run, the longest run each size carries and the three phase formula, use the voltage drop calculator.

The sizes here come from the code tables and the drop math, nothing more. Local amendments, conduit fill, more than three current-carrying wires together, high ambient heat, and motor, HVAC or EV charger nameplate rules can all change the answer. Check your local code and the terminal ratings, and when the job is priced, the electrical pricing guide helps with the number.

Common questions

For 30 A at 60 °C, NEC Table 310.16 calls for 10 AWG copper (rated 30 A) or 8 AWG aluminum (rated 35 A; 10 AWG aluminum is only 25 A). On a long run the voltage drop can push it bigger: 30 A on 240 V over 150 feet needs 8 AWG copper to stay within 3%.

At 60 °C, 6 AWG copper (55 A) or 4 AWG aluminum (55 A). Where the breaker, the device and the wire are all rated 75 °C, 8 AWG copper (50 A) or 6 AWG aluminum (50 A). Long runs may need the next size up for voltage drop.

Find the size the amps need from the code table, then check the voltage drop on that size over the one-way length. If the drop is over 3%, go up a size until it is under. The calculator above does both and gives you the larger size.

For circuits of 100 A and under, and for NM cable, use 60 °C unless every terminal on the circuit (breaker, device and wire) is rated 75 °C. Circuits over 100 A use the 75 °C column (NEC 110.14(C)), so the calculator switches to it above 100 A. Check the labels on the equipment and your local code.

A continuous load runs for 3 hours or more, like an EV charger, a water heater or a heat strip. The wire has to carry 125% of its amps (NEC 210.19(A)(1)), so a 32 A charger is sized as 40 A. The voltage drop is still worked at the 32 A it draws. Enter the load's own amps and pick Continuous above: on 240 V over 120 feet of copper at 60 °C, the 32 A charger needs 8 AWG, which drops 2.5%.

No. The math runs in your browser and nothing you type is sent or stored. There is no account and no email.

More free contractor tools

Volts lost on a long run

Voltage Drop Calculator

Copper or aluminum, single or three phase, with a chart of every size from 14 AWG to 4/0.

Copper or PEX for your flow

Pipe Size Calculator

Water speed in every size of copper and PEX from the GPM, and the smallest pipe under your limit.

Saturation pressure for 4 refrigerants

Refrigerant PT Chart

R-22, R-410A, R-454B and R-32 every 5 °F, with bubble and dew columns for the blends.

A 30% markup is not a 30% margin

Markup vs Margin Calculator

Convert between the two, and find the markup that lands the margin you want.

What to charge per hour

Hourly Rate Calculator

Work back from the take-home you want, your overhead, and the hours you can actually bill.

Price the job while the numbers are fresh

FastEstimateMaker turns the wire, the parts and your labor into an estimate your customer can sign from their phone. Start free - no credit card, no setup call.

Build a real estimate free

Solo is $29.99/month with every office feature. Canvass is $59.99/month plus $19.99/month per rep seat.