Voltage Drop Calculator
Copper or aluminum, single or three phase, with a chart of every size from 14 AWG to 4/0.
Free calculator
Enter the load, the volts and the one-way distance. You get the size the amps need, the size the distance needs, and the wire to use.
AWG numbers run backwards: the smaller the number, the thicker the wire. 14 AWG is the thinnest size this calculator uses and 4/0 (said "four aught") is the thickest. Each size has an area in circular mils, which sets its resistance, and an allowable current from the code tables, which sets how much it can carry without overheating.
| Wire (AWG) | Area (cmil) | Copper 60 °C amps | Copper 75 °C amps | Alum. 60 °C amps | Alum. 75 °C amps |
|---|---|---|---|---|---|
| 14 | 4,110 | 15 | 15 | - | - |
| 12 | 6,530 | 20 | 20 | 15 | 15 |
| 10 | 10,380 | 30 | 30 | 25 | 25 |
| 8 | 16,510 | 40 | 50 | 35 | 40 |
| 6 | 26,240 | 55 | 65 | 40 | 50 |
| 4 | 41,740 | 70 | 85 | 55 | 65 |
| 3 | 52,620 | 85 | 100 | 65 | 75 |
| 2 | 66,360 | 95 | 115 | 75 | 90 |
| 1 | 83,690 | 110 | 130 | 85 | 100 |
| 1/0 | 105,600 | 125 | 150 | 100 | 120 |
| 2/0 | 133,100 | 145 | 175 | 115 | 135 |
| 3/0 | 167,800 | 165 | 200 | 130 | 155 |
| 4/0 | 211,600 | 195 | 230 | 150 | 180 |
The amps assume no more than three current-carrying wires together and 86 °F (30 °C) around them, with the breaker limits of NEC 240.4(D) on 14 to 10 AWG. Area is from NEC Chapter 9, Table 8. A dash means the size is not listed (14 AWG aluminum). The 60 °C columns apply to circuits of 100 A and under and to NM cable, unless every terminal on the circuit is rated 75 °C. Circuits over 100 A use the 75 °C columns (NEC 110.14(C)), and the calculator switches to them above 100 A. Example: 200 A on 240 V, 100 feet, copper, needs 3/0 (200 A at 75 °C), which drops 3.08 V (1.28%).
Aluminum carries less current than copper of the same size and has more resistance (a K of 21.2 against 12.9), so an aluminum run is usually one size larger in the common sizes. Example: 60 A on 240 V, 100 feet, with 75 °C terminals. Copper needs 6 AWG, which drops 5.90 V (2.46%). Aluminum needs 4 AWG, which drops 6.09 V (2.54%).
Aluminum is common for feeders and service wire because it costs less per foot at those sizes. It needs lugs and connectors rated for aluminum (marked AL or AL/CU) and the torque the maker lists. Switch the wire above to compare the two on your own run.
The amps set the smallest size that is safe. The distance can push it bigger, because a thin wire on a long run loses too much voltage. This calculator checks both and gives you the larger:
For a chart of every size on your run, the longest run each size carries and the three phase formula, use the voltage drop calculator.
The sizes here come from the code tables and the drop math, nothing more. Local amendments, conduit fill, more than three current-carrying wires together, high ambient heat, and motor, HVAC or EV charger nameplate rules can all change the answer. Check your local code and the terminal ratings, and when the job is priced, the electrical pricing guide helps with the number.
For 30 A at 60 °C, NEC Table 310.16 calls for 10 AWG copper (rated 30 A) or 8 AWG aluminum (rated 35 A; 10 AWG aluminum is only 25 A). On a long run the voltage drop can push it bigger: 30 A on 240 V over 150 feet needs 8 AWG copper to stay within 3%.
At 60 °C, 6 AWG copper (55 A) or 4 AWG aluminum (55 A). Where the breaker, the device and the wire are all rated 75 °C, 8 AWG copper (50 A) or 6 AWG aluminum (50 A). Long runs may need the next size up for voltage drop.
Find the size the amps need from the code table, then check the voltage drop on that size over the one-way length. If the drop is over 3%, go up a size until it is under. The calculator above does both and gives you the larger size.
For circuits of 100 A and under, and for NM cable, use 60 °C unless every terminal on the circuit (breaker, device and wire) is rated 75 °C. Circuits over 100 A use the 75 °C column (NEC 110.14(C)), so the calculator switches to it above 100 A. Check the labels on the equipment and your local code.
A continuous load runs for 3 hours or more, like an EV charger, a water heater or a heat strip. The wire has to carry 125% of its amps (NEC 210.19(A)(1)), so a 32 A charger is sized as 40 A. The voltage drop is still worked at the 32 A it draws. Enter the load's own amps and pick Continuous above: on 240 V over 120 feet of copper at 60 °C, the 32 A charger needs 8 AWG, which drops 2.5%.
No. The math runs in your browser and nothing you type is sent or stored. There is no account and no email.
See all contractor tools, or jump to estimate software for electricians.
Copper or aluminum, single or three phase, with a chart of every size from 14 AWG to 4/0.
Water speed in every size of copper and PEX from the GPM, and the smallest pipe under your limit.
Suction and liquid pressures plus line temperatures to superheat and subcooling, read on the right line for blends.
R-22, R-410A, R-454B and R-32 every 5 °F, with bubble and dew columns for the blends.
Convert between the two, and find the markup that lands the margin you want.
Work back from the take-home you want, your overhead, and the hours you can actually bill.
FastEstimateMaker turns the wire, the parts and your labor into an estimate your customer can sign from their phone. Start free - no credit card, no setup call.
Build a real estimate freeSolo is $29.99/month with every office feature. Canvass is $59.99/month plus $19.99/month per rep seat.