Superheat and Subcooling Calculator
Suction and liquid pressures plus line temperatures to superheat and subcooling, read on the right line for blends.
Free PT chart
Saturation pressure in psig for the four refrigerants on most service calls, every 5 °F from -20 to 130 °F. Type a gauge reading to get its temperature, or pick a tab to read the chart.
R-22 is a single refrigerant, so it has one pressure for each temperature. It is no longer made new in the US; systems still running on it are serviced with recovered and reclaimed R-22.
| °F | psig |
|---|---|
| −20 | 10.2 |
| −15 | 13.2 |
| −10 | 16.5 |
| −5 | 20.1 |
| 0 | 24.0 |
| 5 | 28.3 |
| 10 | 32.8 |
| 15 | 37.8 |
| 20 | 43.1 |
| 25 | 48.8 |
| 30 | 55.0 |
| 35 | 61.5 |
| 40 | 68.6 |
| 45 | 76.1 |
| 50 | 84.1 |
| 55 | 92.6 |
| 60 | 101.6 |
| 65 | 111.2 |
| 70 | 121.4 |
| 75 | 132.2 |
| 80 | 143.6 |
| 85 | 155.7 |
| 90 | 168.4 |
| 95 | 181.8 |
| 100 | 195.9 |
| 105 | 210.8 |
| 110 | 226.4 |
| 115 | 242.8 |
| 120 | 260.0 |
| 125 | 278.0 |
| 130 | 296.9 |
R-410A is a blend, but its bubble and dew lines sit about 0.2 °F apart (about a psi), so either column works in the field. Use dew for superheat and bubble for subcooling to be exact.
| °F | Bubble (liquid) psig | Dew (vapor) psig |
|---|---|---|
| −20 | 26.3 | 26.2 |
| −15 | 31.2 | 31.0 |
| −10 | 36.5 | 36.3 |
| −5 | 42.2 | 42.0 |
| 0 | 48.4 | 48.2 |
| 5 | 55.2 | 54.9 |
| 10 | 62.4 | 62.2 |
| 15 | 70.3 | 70.0 |
| 20 | 78.7 | 78.4 |
| 25 | 87.7 | 87.4 |
| 30 | 97.4 | 97.0 |
| 35 | 107.7 | 107.3 |
| 40 | 118.8 | 118.4 |
| 45 | 130.6 | 130.1 |
| 50 | 143.1 | 142.6 |
| 55 | 156.5 | 156.0 |
| 60 | 170.7 | 170.1 |
| 65 | 185.8 | 185.1 |
| 70 | 201.7 | 201.1 |
| 75 | 218.6 | 217.9 |
| 80 | 236.5 | 235.7 |
| 85 | 255.4 | 254.6 |
| 90 | 275.3 | 274.5 |
| 95 | 296.4 | 295.4 |
| 100 | 318.5 | 317.6 |
| 105 | 341.9 | 340.8 |
| 110 | 366.5 | 365.4 |
| 115 | 392.3 | 391.2 |
| 120 | 419.5 | 418.3 |
| 125 | 448.0 | 446.8 |
| 130 | 478.0 | 476.8 |
R-454B is an A2L (mildly flammable) blend with about 2 °F of glide. Read the suction pressure on the dew (vapor) column for superheat and the liquid pressure on the bubble (liquid) column for subcooling.
| °F | Bubble (liquid) psig | Dew (vapor) psig |
|---|---|---|
| −20 | 24.3 | 22.6 |
| −15 | 28.9 | 27.0 |
| −10 | 33.9 | 31.8 |
| −5 | 39.4 | 37.0 |
| 0 | 45.3 | 42.7 |
| 5 | 51.7 | 48.8 |
| 10 | 58.5 | 55.4 |
| 15 | 66.0 | 62.6 |
| 20 | 73.9 | 70.3 |
| 25 | 82.5 | 78.5 |
| 30 | 91.7 | 87.4 |
| 35 | 101.5 | 96.9 |
| 40 | 112.0 | 107.0 |
| 45 | 123.1 | 117.8 |
| 50 | 135.0 | 129.3 |
| 55 | 147.7 | 141.6 |
| 60 | 161.1 | 154.6 |
| 65 | 175.4 | 168.5 |
| 70 | 190.5 | 183.1 |
| 75 | 206.5 | 198.7 |
| 80 | 223.4 | 215.2 |
| 85 | 241.2 | 232.6 |
| 90 | 260.0 | 251.0 |
| 95 | 279.9 | 270.4 |
| 100 | 300.8 | 290.9 |
| 105 | 322.8 | 312.5 |
| 110 | 345.9 | 335.2 |
| 115 | 370.2 | 359.1 |
| 120 | 395.7 | 384.3 |
| 125 | 422.4 | 410.8 |
| 130 | 450.5 | 438.7 |
R-32 is a single A2L refrigerant with one line. It runs a little above R-410A: 121.0 psig at 40 °F against 118.8 for R-410A.
| °F | psig |
|---|---|
| −20 | 26.8 |
| −15 | 31.7 |
| −10 | 37.1 |
| −5 | 42.9 |
| 0 | 49.3 |
| 5 | 56.1 |
| 10 | 63.5 |
| 15 | 71.4 |
| 20 | 80.0 |
| 25 | 89.2 |
| 30 | 99.1 |
| 35 | 109.7 |
| 40 | 121.0 |
| 45 | 133.0 |
| 50 | 145.8 |
| 55 | 159.5 |
| 60 | 174.0 |
| 65 | 189.5 |
| 70 | 205.8 |
| 75 | 223.2 |
| 80 | 241.5 |
| 85 | 260.9 |
| 90 | 281.3 |
| 95 | 302.9 |
| 100 | 325.7 |
| 105 | 349.6 |
| 110 | 374.9 |
| 115 | 401.4 |
| 120 | 429.3 |
| 125 | 458.7 |
| 130 | 489.5 |
Saturation temperature is the boiling point of the refrigerant at the pressure on your gauge. Find the pressure in the column for your refrigerant and read the temperature on the same row. Between rows, the lookup above reads between the two 5 °F rows the way pressure really climbs (it rises a little faster the warmer it gets), so it stays within about a tenth of a degree of the published tables.
Example: an R-410A suction gauge reads 120 psig. The dew column has 118.4 psig at 40 °F and 130.1 psig at 45 °F, so 120 psig is about 40.7 °F. The refrigerant in the evaporator is boiling at 40.7 °F, and anything the suction line reads above that is superheat.
The chart is in psig at sea level. Gauges read against the air around them, so at 5,000 feet a gauge reads about 2.5 psi higher for the same refrigerant. Take that off before you read the chart, unless your digital gauges already correct for altitude.
R-410A and R-454B are blends of refrigerants that boil at slightly different temperatures. At one pressure, a blend starts to boil at its bubble point and finishes at its dew point, a little warmer. The gap is called glide.
On R-410A the two lines sit about 0.2 °F apart, about a psi (1.2 psi at the top of the chart), so it hardly matters. R-454B has about 2 °F of glide, and it shows: at 107.0 psig the dew point is 40.0 °F and the bubble point is 37.7 °F. With a 50 °F suction line, that is 10.0 °F of superheat read on the right column, or 12.3 °F read on the wrong one.
At the 40 to 100 °F you read in the field, R-410A runs about 1.6 to 1.7 times the pressure of R-22 at the same temperature. Colder, the gap grows: at 0 °F it is about 2 times. At 40 °F, R-22 is 68.6 psig and R-410A is 118.8 psig. At 100 °F, R-22 is 195.9 psig and R-410A is 318.5 psig. The oils differ too (mineral oil against POE), so R-410A never goes into an R-22 system, and gauges, hoses and recovery gear have to be rated for R-410A pressures.
R-454B runs a little lower than R-410A, about 5 to 10% at the same temperature across the 40 to 100 °F you read in the field, and more in the cold (about 14% on the dew line at -20 °F). At 40 °F the R-454B dew point is 107.0 psig against 118.4 for R-410A, and at 100 °F its bubble point is 300.8 psig against 318.5. That is close enough that the gauges look familiar and far enough to matter: 107.0 psig read on an R-410A chart is about 34.9 °F, five degrees off. R-454B is not a drop-in for R-410A. It is an A2L refrigerant for equipment built for it, with its own charging chart.
Superheat and subcooling are the two numbers that tell you whether the charge is right, and both start from this chart. The superheat and subcooling calculator takes your suction and liquid pressures and line temperatures and reads the right line for you. When the repair is clear, put it on an HVAC estimate, and see the HVAC service pricing guide for how to price the call.
The pressures come from greencalculus.com (CoolProp and Chemours, CC BY 4.0). R-22, R-410A and R-32 are calculated with CoolProp; R-454B uses Chemours data (REFPROP 10). We list them every 5 °F from -20 to 130 °F, in psig at sea level, rounded to 0.1 psi. They are saturation values for pure, new refrigerant. The equipment maker's charging chart is the last word on any system.
At sea level, R-410A at 40 °F is 118.8 psig on the bubble (liquid) line and 118.4 psig on the dew (vapor) line. For superheat use the dew number: a suction gauge reading 118.4 psig means the refrigerant is boiling at 40 °F.
R-22 at 40 °F is 68.6 psig at sea level. R-22 is a single refrigerant, so it has one pressure for each temperature. R-410A at the same temperature is about 1.7 times higher.
R-454B is a blend with about 2 °F of glide: at one pressure it starts to boil at the bubble point and finishes at the dew point. Read the suction pressure on the dew (vapor) column for superheat and the liquid pressure on the bubble (liquid) column for subcooling.
No. At the 40 to 100 °F of a running system, R-454B runs about 5 to 10% lower pressure than R-410A, and it is an A2L (mildly flammable) refrigerant, so it goes in equipment built and listed for it, with its own charging chart. Do not top off or convert an R-410A system with it.
psig at sea level. At altitude the air presses less, so a gauge reads higher for the same refrigerant: about 2.5 psi higher at 5,000 feet. Take that off the reading before you use the chart, unless your digital gauges correct for altitude.
It turns a gauge pressure into the temperature the refrigerant is boiling or condensing at, which you need for superheat and subcooling. It also checks a recovery cylinder at rest: its pressure should match the room temperature on the chart, and a higher pressure points to air or a mixed refrigerant.
See all contractor tools, or the free HVAC estimate template.
Suction and liquid pressures plus line temperatures to superheat and subcooling, read on the right line for blends.
Copper or aluminum, single or three phase, with a chart of every size from 14 AWG to 4/0.
The smallest copper or aluminum wire, 14 AWG to 4/0, for the load and the run.
Water speed in every size of copper and PEX from the GPM, and the smallest pipe under your limit.
Convert between the two, and find the markup that lands the margin you want.
Work back from the take-home you want, your overhead, and the hours you can actually bill.
FastEstimateMaker writes the HVAC estimate from what you found, sends it to the customer's phone and gets it signed before you leave the driveway. Your first 2 jobs are free, start to finish, with no credit card.
Build a real estimate freeSolo is $29.99/month with every office feature. Canvass is $59.99/month plus $19.99/month per rep seat.