R-22, R-410A, R-454B and R-32 every 5 °F, with bubble and dew columns for the blends.
Free HVAC calculator
Enter the suction and liquid pressures from your gauges and the line temperatures. You get superheat and subcooling, read on the dew and bubble lines for blends like R-410A and R-454B.
Each reading alone says little. Together, superheat and subcooling point to what is wrong with the system, and the pressures on the gauges narrow it down:
| Superheat | Subcooling | Often points to |
|---|---|---|
| High | Low | Low charge or a leak, with low pressures on both sides |
| Low | High | Overcharge, with high head pressure |
| High | High | A restriction: the filter drier, the liquid line or the metering device |
| Low | Normal | Low airflow or load on the indoor coil, with low suction pressure |
Check airflow first: a dirty filter, a dirty coil or a slow blower moves both numbers, and it is the cheaper fix. Fixed orifice (piston) systems are charged by superheat against the maker's chart, which uses the indoor wet bulb and the outdoor temperature. TXV and EEV systems are charged by subcooling, usually to the number on the data plate. This calculator does the conversion; the target comes from the equipment.
Superheat tells you how far past boiling the gas leaving the evaporator is. Subcooling tells you how far below condensing the liquid leaving the condenser is. Both start the same way: turn a gauge pressure into a saturation temperature, then compare it with the temperature of the line.
Example on R-410A: the suction gauge reads 118.4 psig, which is 40.0 °F on the dew line. The suction line reads 50 °F, so superheat is 10.0 °F. The liquid gauge reads 341.9 psig, which is 105.0 °F on the bubble line. The liquid line reads 95 °F, so subcooling is 10.0 °F. Those are the numbers the calculator opens with.
On a blend with glide, the line matters. R-454B liquid at 322.8 psig is 105.0 °F on the bubble line, so a 95 °F liquid line is 10.0 °F of subcooling. Read on the dew line it would look like 12.3 °F. The calculator picks the dew line for superheat and the bubble line for subcooling.
Take readings after the system has run about 15 minutes, with the pressure and the temperature at the same moment. Clamp the thermometer to clean bare copper and insulate the clamp so outdoor air does not skew it.
Need the whole table? The refrigerant PT chart lists R-22, R-410A, R-454B and R-32 every 5 °F from -20 to 130 °F, with bubble and dew columns for the blends. Jump straight to R-410A or R-454B.
Pressure data: greencalculus.com (CoolProp and Chemours, CC BY 4.0), in psig at sea level. To price the call once you know the fix, see the HVAC service pricing guide.
Superheat is how many degrees the suction line is above the saturation temperature at the suction pressure. On R-410A, 118.4 psig is 40 °F, so a 50 °F suction line is 10 °F of superheat. It shows how much of the evaporator is still boiling refrigerant, and it keeps liquid out of the compressor.
Subcooling is how many degrees the liquid line is below the saturation temperature at the liquid pressure. On R-410A, 341.9 psig is 105 °F, so a 95 °F liquid line is 10 °F of subcooling. It shows how much liquid is backed up in the condenser, which is why TXV systems are charged by it.
Superheat uses the dew (vapor) line at the suction pressure. Subcooling uses the bubble (liquid) line at the liquid pressure. On R-454B the two are about 2 °F apart, enough to throw a reading off; on R-410A they are within half a degree.
Fixed orifice (piston) systems: superheat, against the maker's chart for the indoor wet bulb and outdoor temperature. TXV and EEV systems: subcooling, to the target on the data plate. The maker's charging instructions win over any rule of thumb.
The target for a piston system depends on the indoor wet bulb and the outdoor temperature, and the maker's chart sets it. This calculator gives the actual superheat and subcooling from your gauges so you can compare them with that target.
No. Nothing you type is transmitted or stored. The math runs in your browser from the same pressure tables as the PT chart.
See all contractor tools, or jump to the free HVAC estimate template.
R-22, R-410A, R-454B and R-32 every 5 °F, with bubble and dew columns for the blends.
Copper or aluminum, single or three phase, with a chart of every size from 14 AWG to 4/0.
The smallest copper or aluminum wire, 14 AWG to 4/0, for the load and the run.
Water speed in every size of copper and PEX from the GPM, and the smallest pipe under your limit.
Convert between the two, and find the markup that lands the margin you want.
Work back from the take-home you want, your overhead, and the hours you can actually bill.
FastEstimateMaker writes the HVAC estimate from what you found, sends it to the customer's phone and gets it signed before you leave the driveway. Your first 2 jobs are free, start to finish, with no credit card.
Build a real estimate freeSolo is $29.99/month with every office feature. Canvass is $59.99/month plus $19.99/month per rep seat.