Enter the volts, amps, one-way length and wire size. You get the volts lost, the percent drop, the voltage at the load and the smallest wire that stays within 3%.
Every foot of wire has resistance, so some of the voltage at the panel never reaches the load. Lights dim, motors run hot and chargers slow down. The longer the run and the bigger the load, the more you lose, and a bigger wire is how you get it back.
Single phase:
VD = 2 x K x I x L / CM
Three phase:
VD = 1.732 x K x I x L / CM
Worked example: a 20 A load on 120 V, 100 feet from the panel, on 12 AWG copper. 2 x 12.9 x 20 x 100 = 51,600. Divide by 6,530 and you lose 7.90 volts, which is 6.58% of 120. The load sees 112.1 V. The calculator opens with these numbers.
The same run on every size from 14 AWG to 4/0. It follows the calculator above as you type. Rows over your limit are marked, and the last column is the longest one-way run each size carries at that load.
| Wire (AWG) | Volts lost | Drop | At the load | Longest run at 3% |
|---|---|---|---|---|
| 14 | 12.55 V | 10.46% (over) | 107.4 V | 28 ft |
| 12 (yours) | 7.90 V | 6.58% (over) | 112.1 V | 45 ft |
| 10 | 4.97 V | 4.14% (over) | 115.0 V | 72 ft |
| 8 | 3.13 V | 2.60% | 116.9 V | 115 ft |
| 6 | 1.97 V | 1.64% | 118.0 V | 183 ft |
| 4 | 1.24 V | 1.03% | 118.8 V | 291 ft |
| 3 | 0.98 V | 0.82% | 119.0 V | 367 ft |
| 2 | 0.78 V | 0.65% | 119.2 V | 462 ft |
| 1 | 0.62 V | 0.51% | 119.4 V | 583 ft |
| 1/0 | 0.49 V | 0.41% | 119.5 V | 736 ft |
| 2/0 | 0.39 V | 0.32% | 119.6 V | 928 ft |
| 3/0 | 0.31 V | 0.26% | 119.7 V | 1,170 ft |
| 4/0 | 0.24 V | 0.20% | 119.8 V | 1,476 ft |
For the 20 A, 100 foot run, 10 AWG still loses 4.97 V (4.14%). 8 AWG is the first size within 3%: 3.13 V, 2.6%, with 116.9 V at the load.
Single phase current goes out on one wire and back on another, so the formula doubles the length. On balanced three phase the currents share the return, so the factor is 1.732 (the square root of 3) instead of 2. The same wire and load drops about 13% less.
Example: 40 A on 208 V three phase, 150 feet of 8 AWG copper. 1.732 x 12.9 x 40 x 150 / 16,510 = 8.12 V, or 3.9%, leaving 199.9 V at the load. Run the same numbers as single phase and the drop is 9.38 V (4.51%).
Informational notes in the National Electrical Code suggest no more than 3% drop on a branch circuit and 5% for the feeder and branch together. They are advice, not rules, unless your local code adopts them, but most inspectors work to them.
When a run is over, four ways back under:
From the longest-run column: 12 AWG copper at 20 A on 120 V stays within 3% for 45 feet. Past that, size up.
The chart checks drop only. Whether a wire can carry the amps comes from the code's ampacity tables: the calculator's last row checks them at 60 °C for 100 A and under and 75 °C over 100 A, and the wire size calculator adds 75 °C terminals on smaller circuits and continuous loads. For pricing, see the electrical pricing guide.
For single phase, voltage drop = 2 x K x I x L / CM, where K is 12.9 for copper or 21.2 for aluminum, I is the amps, L is the one-way length in feet and CM is the wire area in circular mils. For three phase, use 1.732 in place of the 2. Divide the result by the supply voltage for the percent drop.
The NEC informational notes recommend no more than 3% on a branch circuit and 5% total for the feeder and branch circuit together. They are recommendations rather than requirements unless your local code adopts them. Some equipment, like motors and EV chargers, may ask for less in the installation instructions.
At a full 20 A on 120 V, 12 AWG copper stays within 3% drop for about 45 feet one way. On 240 V the same wire and load reaches about 91 feet. A lighter load goes farther: the run scales with the amps, so 10 A on 120 V reaches about 91 feet.
Yes, for the same wire, amps and length. Single phase multiplies by 2 for the out and back trip; balanced three phase multiplies by the square root of 3, about 1.732. That is about 13% less drop.
Yes. Aluminum has a K of 21.2 against 12.9 for copper, so the same size drops about 64% more. That is one reason aluminum runs are usually one size larger than copper, like 8 AWG aluminum where copper would be 10 AWG.
No. The math runs in your browser and nothing you type is sent or stored. There is no account and no email.
See all contractor tools, or jump to estimate software for electricians.
Suction and liquid pressures plus line temperatures to superheat and subcooling, read on the right line for blends.
The smallest copper or aluminum wire, 14 AWG to 4/0, for the load and the run.
R-22, R-410A, R-454B and R-32 every 5 °F, with bubble and dew columns for the blends.
Water speed in every size of copper and PEX from the GPM, and the smallest pipe under your limit.
Convert between the two, and find the markup that lands the margin you want.
Work back from the take-home you want, your overhead, and the hours you can actually bill.
FastEstimateMaker puts the wire, the breaker and your labor on a clean estimate your customer can sign from their phone. Start free - no credit card, no setup call.
Build a real estimate freeSolo is $29.99/month with every office feature. Canvass is $59.99/month plus $19.99/month per rep seat.