Free calculator

Voltage Drop Calculator

Enter the volts, amps, one-way length and wire size. You get the volts lost, the percent drop, the voltage at the load and the smallest wire that stays within 3%.

Your circuit

Volts lost on your run

Enter the run the way you will wire it. Nothing you type leaves your browser.

System
Wire
V

Common: 120, 208, 240, 277, 480.

A

The current the load draws.

ft

Panel to the load. The formula counts the return trip for you.

AWG, from 14 (thinnest) to 4/0.

%

3% is the usual target for a branch circuit, 5% for feeder and branch together.

Result

-

Fill in the run above.

Volts lost-
Drop-
Volts at the load-
Longest run for this wire at 3%-
Smallest wire within 3% (drop only)-
Smallest wire for 20 A and 3%-

The last row also checks that the wire carries the amps, from NEC Table 310.16 at 60 °C for 100 A and under and 75 °C over 100 A. For 75 °C terminals on smaller circuits and continuous loads, use the wire size calculator. See every size for this run.

The voltage drop formula

Every foot of wire has resistance, so some of the voltage at the panel never reaches the load. Lights dim, motors run hot and chargers slow down. The longer the run and the bigger the load, the more you lose, and a bigger wire is how you get it back.

Single phase:
VD = 2 x K x I x L / CM

Three phase:
VD = 1.732 x K x I x L / CM

  • K is the resistance of the metal: 12.9 for copper, 21.2 for aluminum (ohm-circular mils per foot).
  • I is the load in amps.
  • L is the length of the run one way, in feet. The 2 counts the trip back.
  • CM is the wire's area in circular mils: 6,530 for 12 AWG, 16,510 for 8 AWG (NEC Chapter 9, Table 8).

Worked example: a 20 A load on 120 V, 100 feet from the panel, on 12 AWG copper. 2 x 12.9 x 20 x 100 = 51,600. Divide by 6,530 and you lose 7.90 volts, which is 6.58% of 120. The load sees 112.1 V. The calculator opens with these numbers.

Voltage drop chart by wire size

The same run on every size from 14 AWG to 4/0. It follows the calculator above as you type. Rows over your limit are marked, and the last column is the longest one-way run each size carries at that load.

Copper, single phase, 120 V, 20 A, 100 ft one way. Your limit: 3%.
Wire (AWG)Volts lostDropAt the loadLongest run at 3%
1412.55 V10.46% (over)107.4 V28 ft
12 (yours)7.90 V6.58% (over)112.1 V45 ft
104.97 V4.14% (over)115.0 V72 ft
83.13 V2.60%116.9 V115 ft
61.97 V1.64%118.0 V183 ft
41.24 V1.03%118.8 V291 ft
30.98 V0.82%119.0 V367 ft
20.78 V0.65%119.2 V462 ft
10.62 V0.51%119.4 V583 ft
1/00.49 V0.41%119.5 V736 ft
2/00.39 V0.32%119.6 V928 ft
3/00.31 V0.26%119.7 V1,170 ft
4/00.24 V0.20%119.8 V1,476 ft

For the 20 A, 100 foot run, 10 AWG still loses 4.97 V (4.14%). 8 AWG is the first size within 3%: 3.13 V, 2.6%, with 116.9 V at the load.

Single phase vs three phase

Single phase current goes out on one wire and back on another, so the formula doubles the length. On balanced three phase the currents share the return, so the factor is 1.732 (the square root of 3) instead of 2. The same wire and load drops about 13% less.

Example: 40 A on 208 V three phase, 150 feet of 8 AWG copper. 1.732 x 12.9 x 40 x 150 / 16,510 = 8.12 V, or 3.9%, leaving 199.9 V at the load. Run the same numbers as single phase and the drop is 9.38 V (4.51%).

Keeping drop under 3%

Informational notes in the National Electrical Code suggest no more than 3% drop on a branch circuit and 5% for the feeder and branch together. They are advice, not rules, unless your local code adopts them, but most inspectors work to them.

When a run is over, four ways back under:

  • Go up a wire size. Each step up cuts the drop by about a fifth to over a third.
  • Raise the voltage. The same watts at 240 V take half the amps, and the percent drop falls to a quarter.
  • Shorten the run or move the panel or subpanel closer.
  • Split the load across two circuits.

From the longest-run column: 12 AWG copper at 20 A on 120 V stays within 3% for 45 feet. Past that, size up.

The chart checks drop only. Whether a wire can carry the amps comes from the code's ampacity tables: the calculator's last row checks them at 60 °C for 100 A and under and 75 °C over 100 A, and the wire size calculator adds 75 °C terminals on smaller circuits and continuous loads. For pricing, see the electrical pricing guide.

Common questions

For single phase, voltage drop = 2 x K x I x L / CM, where K is 12.9 for copper or 21.2 for aluminum, I is the amps, L is the one-way length in feet and CM is the wire area in circular mils. For three phase, use 1.732 in place of the 2. Divide the result by the supply voltage for the percent drop.

The NEC informational notes recommend no more than 3% on a branch circuit and 5% total for the feeder and branch circuit together. They are recommendations rather than requirements unless your local code adopts them. Some equipment, like motors and EV chargers, may ask for less in the installation instructions.

At a full 20 A on 120 V, 12 AWG copper stays within 3% drop for about 45 feet one way. On 240 V the same wire and load reaches about 91 feet. A lighter load goes farther: the run scales with the amps, so 10 A on 120 V reaches about 91 feet.

Yes, for the same wire, amps and length. Single phase multiplies by 2 for the out and back trip; balanced three phase multiplies by the square root of 3, about 1.732. That is about 13% less drop.

Yes. Aluminum has a K of 21.2 against 12.9 for copper, so the same size drops about 64% more. That is one reason aluminum runs are usually one size larger than copper, like 8 AWG aluminum where copper would be 10 AWG.

No. The math runs in your browser and nothing you type is sent or stored. There is no account and no email.

More free contractor tools

What gauge for the amps and distance

Wire Size Calculator

The smallest copper or aluminum wire, 14 AWG to 4/0, for the load and the run.

Saturation pressure for 4 refrigerants

Refrigerant PT Chart

R-22, R-410A, R-454B and R-32 every 5 °F, with bubble and dew columns for the blends.

Copper or PEX for your flow

Pipe Size Calculator

Water speed in every size of copper and PEX from the GPM, and the smallest pipe under your limit.

A 30% markup is not a 30% margin

Markup vs Margin Calculator

Convert between the two, and find the markup that lands the margin you want.

What to charge per hour

Hourly Rate Calculator

Work back from the take-home you want, your overhead, and the hours you can actually bill.

Turn the run into a signed job

FastEstimateMaker puts the wire, the breaker and your labor on a clean estimate your customer can sign from their phone. Start free - no credit card, no setup call.

Build a real estimate free

Solo is $29.99/month with every office feature. Canvass is $59.99/month plus $19.99/month per rep seat.